PHV RANGE
|
 |
Technical data
| Technical data recessed
|
- Mounting height surface mounted 4m
- Mounting Height recessed 3.75m
- 3-way valve (water units)
- Available in Electric, Water and Ambient
- Tangential fans
- Optional remote thermostat
- Optional schedule automation
- Optional door contact switch
|
Scope of Application
The PHV range of units are suitable for installations where a more powerful air barrier is desired due to a higher volume of traffic such as: department stores, cinemas, high street shops, or even grocery store vestibules when employee and customer comfort is paramount due to extreme climate conditions. PHV units are high velocity and high output units that make them suitable for industrial applications such as food processing plants, factories and warehouses. PHV units are ideally suited for shipping and receiving doors where an air barrier is necessary in saving energy costs.
Features
The surface mounted PHV range NT air curtain has a streamlined steel casing with plastic end caps. The recessed model is supplied with an anodized aluminum grille. The aerodynamic design and tangential fans produce an optimal and uniform airflow creating a wall of air that allows unobstructed traffic through the air door.
Controls
All PHV range NT air curtains are supplied standard with a wall mounted slide switch controller. A remote thermostat, or automation protocol, or door contact switch can be incorporated.
|
|
PHV RANGE NT |
Mounting Height Max. 4.0m
|
|
Models
Metric
Imperial
|
Dimensions (mm) (in) |
Supply (60Hz) |
# Motors @HP |
Heat Output (kW) (Btu/hr) |
Loading (A) *per phase |
Max. Velocity (m/s) (ft/min) |
Max. Air Volume (m³/h) (ft³/min) |
Weight (kg) (Ibs) |
dB(A) @3m |
| |
|
|
|
|
|
|
|
|
|
| Ambient 120V |
| PHV1000A NT |
1196(l) x 377(d) x 255(h) 47(l) x 15(d) x 10(h) |
120V~1P&N |
1@1/4 |
- |
3.2 |
11.5 2,260 |
2,880 1,700 |
30 66 |
59 |
| PHV1500A NT |
1746(l) x 377(d) x 255(h) 69(l) x 15(d) x 10(h) |
120V~1P&N |
1@1/3 |
- |
5.0 |
11.5 2,260 |
4,020 2,370 |
47 104 |
60 |
| PHV2000A NT |
2296(l) x 377(d) x 255(h) 90(l) x 15(d) x 10(h) |
120V~1P&N |
2@1/4 |
- |
6.5 |
11.5 2,260 |
5,760 3,390 |
62 137 |
61 |
| Electric 208V |
| PHV1000E NT |
1196(l) x 377(d) x 255(h) 47(l) x 15(d) x 10(h) |
208V~3P&N |
1@1/4 |
6/12 20,490/40,980 |
37 |
11.5 2,260 |
2,880 1,700 |
31 68 |
59 |
| PHV1500E NT |
1746(l) x 377(d) x 255(h) 69(l) x 15(d) x 10(h) |
208V~3P&N |
1@1/3 |
9/18 30,735/61,470 |
55 |
11.5 2,260 |
4,020 2,370 |
48 106 |
60 |
| PHV2000E NT |
2296(l) x 377(d) x 255(h) 90(l) x 15(d) x 10(h) |
208V~3P&N |
2@1/4 |
12/24 40,980/81,970 |
73 |
11.5 2,206 |
5,760 3,390 |
64 140 |
61 |
| LPHW 120V |
| PHV1000W NT |
1196(l) x 377(d) x 255(h) 47(l) x 15(d) x 10(h) |
120V~1P&N |
1@1/4 |
12 40,490 |
3.2 |
11.0 2,170 |
2,630 1,550 |
32 70 |
59 |
| PHV1500W NT |
1746(l) x 377(d) x 255(h) 69(l) x 15(d) x 10(h) |
120V~1P&N |
1@1/3 |
18 61,470 |
5.0 |
11.0 2,170 |
3,670 2,160 |
50 110 |
60 |
| PHV2000W NT |
2296(l) x 377(d) x 255(h) 90(l) x 15(d) x 10(h) |
120V~1P&N |
2@1/4 |
24 81,970 |
6.5 |
11.0 2,170 |
5,260 3,095 |
66 145 |
61 |
| Electric 600V |
| PHV1000E NT |
1196(l) x 377(d) x 255(h) 47(l) x 15(d) x 10(h) |
600V~3P&N |
1@1/4 |
6/12 20,490/40,980 |
12.7 |
11.5 2,260 |
2,880 1,770 |
29 64 |
59 |
| PHV1500E NT |
1746(l) x 377(d) x 255(h) 69(l) x 15(d) x 10(h) |
600V~3P&N |
1@1/3 |
9/18 30,735/61,470 |
19.5 |
11.5 2,260 |
4,020 2,370 |
45 100 |
60 |
| PHV2000E NT |
2296(l) x 377(d) x 255(h) 90(l) x 15(d) x 10(h) |
600V~3P&N |
2@1/4 |
12/24 40,980/81,970 |
25.4 |
11.5 2,260 |
5,760 3,390 |
61 135 |
61 |
Electric units require a “4 wire + ground” electric supply cable to allow for the hook up of N (neutral). Noise levels are given as a guide only. Variations from this can arise depending on the size of the room the unit is installed in, its acoustic characteristics and the position of the listener.
|
|
| |
PHV RANGE RECESSED |
Mounting Height Max. 3.75m
|
|
Models
Metric
Imperial
|
Dimensions (mm) (in) |
Grille Size inc. Flange (mm) |
Supply (60Hz) |
# Motors @HP |
Heat Output (kW) (Btu/hr) |
Loading (A) *per phase |
Max. Velocity (m/s) (ft/min) |
Max. Air Volume (m³/h) (ft³/min) |
Weight (kg) (Ibs) |
dB(A) @3m |
| |
|
|
|
|
|
|
|
|
|
|
| Ambient 120V |
| PHV1000AR |
1150(l) x 436(d) x 296(h) 45(l) x 17(d) x 12(h) |
1104 x 436 |
120V~1P&N |
1@1/4 |
- |
3.2 |
11.0 2,170 |
2,750 1,620 |
38 84 |
59 |
| PHV1500AR |
1650(l) x 436(d) x 296(h) 65(l) x 17(d) x 12(h) |
1604 x 436 |
120V~1P&N |
1@1/3 |
- |
5.0 |
11.0 2,170 |
3,840 2,260 |
51 112 |
60 |
| PHV2000AR |
2240(l) x 436(d) x 296(h) 88(l) x 17(d) x 12(h) |
2190 x 436 |
120V~1P&N |
2@1/4 |
- |
6.5 |
11.0 2,170 |
5,500 3,240 |
68 150 |
61 |
| Electric 208V |
| PHV1000ER |
1150(l) x 436(d) x 296(h) 45(l) x 17(d) x 12(h) |
1104 x 436 |
208V~3P&N |
1@1/4 |
6/12 20,490/40,980 |
12.6 |
11.0 2,170 |
2,750 1,620 |
42 93 |
59 |
| PHV1500ER |
1650(l) x 436(d) x 296(h) 65(l) x 17(d) x 12(h) |
1604 x 436 |
208V~3P&N |
1@1/3 |
9/18 30,735/61,470 |
18.7 |
11.0 2,170 |
3,840 2,260 |
57 126 |
60 |
| PHV2000ER |
2240(l) x 436(d) x 296(h) 88(l) x 17(d) x 12(h) |
2109 x 436 |
208V~3P&N |
2@1/4 |
12/24 40,980/81,970 |
25.1 |
11.0 2,170 |
5,500 3,240 |
76 168 |
61 |
| LPHW 120V |
| PHV1000WR |
1150(l) x 436(d) x 296(h) 45(l) x 17(d) x 12(h) |
1104 x 436 |
120V~1P&N |
1@1/4 |
12 40,490 |
3.2 |
10.5 2,060 |
2,500 1,470 |
45 99 |
59 |
| PHV1500WR |
1650(l) x 436(d) x 296(h) 65(l) x 17(d) x 12(h) |
1604 x 436 |
120V~1P&N |
1@1/3 |
18 61,470 |
5.0 |
10.5 2,060 |
3,500 2,060 |
59 130 |
60 |
| PHV2000WR |
2240(l) x 436(d) x 296(h) 88(l) x 17(d) x 12(h) |
2190 x 436 |
120V~1P&N |
2@1/4 |
24 81,970 |
6.5 |
10.5 2,060 |
5010 2,950 |
78 172 |
61 |
| Electric 600V |
| PHV1000ER |
1150(l) x 436(d) x 296(h) 45(l) x 17(d) x 12(h) |
1104 x 436 |
600V~3P&N |
1@1/4 |
6/12 20,490/40,980 |
12.7 |
11.0 2,170 |
2,750 1,620 |
42 93 |
59 |
| PHV1500ER |
1650(l) x 436(d) x 296(h) 65(l) x 17(d) x 12(h) |
1604 x 436 |
600V~3P&N |
1@1/3 |
9/18 30,735/61,470 |
19.5 |
11.0 2,170 |
3,840 2,260 |
57 126 |
60 |
| PHV2000ER |
2240(l) x 436(d) x 296(h) 88(l) x 17(d) x 12(h) |
2190 x 436 |
600V~3P&N |
2@1/4 |
12/24 40,980/81,970 |
25.4 |
11.0 2,170 |
5,500 3,240 |
76 168 |
61 |